1、系统开启时指针不动产生的原因:介质中含有杂质,使转子卡住;系统工作压力太小,致使仪表不正常工作。 解决办法::清除异物;增加磁过滤器,增加系统工作压力。
1、差压管路堵塞,疏通差压管路; 2、差压计故障,检查差压计; 3、差压变送器示值明显偏离,应检查尺示值; 4、节流元件安装方向有误,重新安装节流元件;
1. The transmitter of the vortex flowmeter stops the abnormal whistling sound: (1) The flow rate is too high, causing the generator or detection element to vibrate; (2) Cavitation occurs in the pipeline; (3) The generating body or detecting element is loose. Solution: In order to avoid damage to the generating body or detection components, the valve should be adjusted first to reduce the flow rate and the flow rate, and then further investigate the cause.
1. The vortex flowmeter is powered on, the valve is not open, and there is signal output. Solution: ①The shielding or grounding of the output signal of the sensor (or detection element) is poor, which induces external electromagnetic interference; ②The meter is too close to the strong current equipment or high-frequency equipment, and the space electromagnetic radiation interference will affect the meter;
电磁流量计应用领域广泛。大口径仪表较多应用于给排水工程。 中小口径常用于固液双相等难测流体或高要求场所,如测量造纸工业纸浆和黑液、有色冶金业的矿浆、选煤厂的煤浆等。
流量计种类很多,不同的介质对应不同的流量计,非要说电磁流量计性能是很好的,而超声波流量计性能是不好的,不能这样定论,选择一款流量计有好多的标准,所以我们要区别对待。